5 SETTINGS
LATCHED
From user-programmable
pushbuttons logic
sheet 1, 842021A3
LATCHED/SELF-RESET
PUSHBUTTON ON
SETTING
Message Priority
Instantaneous reset will be executed if any
front panel button is pressed or any new
target or message becomes active.
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON
PUSHBUTTON 3 ON
PUSHBUTTON 16 ON
The enhanced front panel has 16 operands;
the standard front panel has 12
Figure 5–10: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 2 of 2)
User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered
separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via
NOTE
EnerVista UR Setup with the Maintenance > Enable Pushbutton command.
PATH: SETTINGS
PRODUCT SETUP
FLEX STATE
PARAMETERS
MESSAGE
MESSAGE
This feature provides a mechanism where any of 256 selected FlexLogic™ operand states can be used for efficient moni-
toring. The feature allows user-customized access to the FlexLogic™ operand states in the relay. The state bits are packed
so that 16 states may be read out in a single Modbus register. The state bits can be configured so that all of the states
which are of interest to the user are available in a minimum number of Modbus registers.
GE Multilin
AND
OR
AND
The message is temporarily removed if
any keypad button is pressed. Ten (10)
seconds of keypad inactivity restores
the message.
AND
= Disabled
= High Priority
= Normal
AND
FLEXLOGIC OPERAND
ANY PB ON
OR
FLEX STATE PARAMETERS
PARAMETER
1:
Off
PARAMETER
2:
Off
PARAMETER 256:
Off
L30 Line Current Differential System
SETTING
Flash Message Time
0
T
RST
Instantaneous
reset *
OR
SETTING
Flash Message Time
0
T
RST
Instantaneous
reset *
PUSHBUTTON 1 LED LOGIC
1. If pushbutton 1 LED control is set to off.
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
2. If pushbutton 1 LED control is not set to off.
SETTING
PUSHBTN 1 LED CTL
= any FlexLogic operand
5.2.14 FLEX STATE PARAMETERS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5.2 PRODUCT SETUP
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
Top Text
= XXXXXXXXXX
On Text
= XXXXXXXXXX
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
Top Text
= XXXXXXXXXX
On Text
= XXXXXXXXXX
5
Pushbutton 1
LED
Pushbutton 1
LED
842024A2.CDR
5-51