Installing Power Distribution Unit (2U) - Fujitsu ETERNUS AF250 S2 Configuration Manual

All-flash arrays storage
Hide thumbs Also See for ETERNUS AF250 S2:
Table of Contents

Advertisement

Chapter 2
Rack Installation
2.1
Power Distribution Unit Installation (for Regions other than the EMEIA, Central American, and Caribbean Regions)
2.1.2

Installing Power Distribution Unit (2U)

This section explains how to install a 2U power distribution unit (12 outlet type or 16 outlet type) in a rack.
This section explains how to install a 12 outlet type power distribution unit as an example. This installa-
tion method can also be applied to a 16 outlet type power distribution unit.
1
Attach the M5 cage nuts to the rear rack pillar.
Attachment positions
On either side, insert eight M5 cage nuts in the 1st, 3rd, 4th, and 6th holes above the power distribu-
tion unit base line.
M5 cage nut
6th hole
4th hole
3rd hole
1st hole
Attachment procedure
Clip the M5 cage nut tabs into the desired hole from the inside.
Side view
(Rack pillar: rear)
[Left]
1U
Power distribution unit
2U
1U
Power distribution unit
Power distribution unit
base line
M5 cage nut
Rack pillar (square hole)
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays Configuration Guide (Basic)
Copyright 2017 FUJITSU LIMITED
M5 cage nut
[Right]
6th hole
4th hole
3rd hole
1st hole
26