Chapter 2
Rack Installation
2.1
Power Distribution Unit Installation (for Regions other than the EMEIA, Central American, and Caribbean Regions)
2.1.2
Installing Power Distribution Unit (2U)
This section explains how to install a 2U power distribution unit (12 outlet type or 16 outlet type) in a rack.
This section explains how to install a 12 outlet type power distribution unit as an example. This installa-
tion method can also be applied to a 16 outlet type power distribution unit.
1
Attach the M5 cage nuts to the rear rack pillar.
Attachment positions
•
On either side, insert eight M5 cage nuts in the 1st, 3rd, 4th, and 6th holes above the power distribu-
tion unit base line.
M5 cage nut
6th hole
4th hole
3rd hole
1st hole
•
Attachment procedure
Clip the M5 cage nut tabs into the desired hole from the inside.
Side view
(Rack pillar: rear)
[Left]
1U
Power distribution unit
2U
1U
Power distribution unit
Power distribution unit
base line
M5 cage nut
Rack pillar (square hole)
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays Configuration Guide (Basic)
Copyright 2017 FUJITSU LIMITED
M5 cage nut
[Right]
6th hole
4th hole
3rd hole
1st hole
26
P3AG-1832-04ENZ0