Levelflex FMP55 FOUNDATION Fieldbus
Endress+Hauser
8.2.6
Write protection via write protection switch
Unlike parameter write protection via a user-specific access code, this allows write access
to the entire operating menu - except for the "Contrast display" parameter - to be locked.
The parameter values are now read only and cannot be edited any more (exception
"Contrast display" parameter):
• Via local display
• Via FOUNDATION Fieldbus
1. Loosen the securing clamp.
2. Unscrew the housing cover.
3. Pull out the display module with a gentle rotation movement. To make it easier to
access the lock switch, attach the display module to the edge of the electronics
compartment.
Display module is attached to the edge of the electronics compartment.
ON
OFF
CDI
WP
SIM
XXXXXXXXXXXXX
Operation options
WP SIM
3 mm
2.5 Nm (1.84 lbf ft)
A0021474
A0013909
51