Function Blocks
PI Pulse Input
Hints
If it is necessary to turn off a device when the pulse counter is placed in HOLD, it is recommended that you
also tie the source of the input HOLD signal to a DO block. The DO block would then control the On/off
State of the device.
Configuration Parameters
Properties Group
Parameter
Block
Order
Address
Rack
Module
Channel
Pulse Weight
Pulses per EU
Rate
Sample Time
Time Period
264

Table 77 Pulse Input Configuration Parameters

Index #
N/A
0
0
0
1
5
6
HC900 Hybrid Control Designer Function Block Reference Guide
Description
Execution Order for
Block.
This is the rack
address of the PFQ
module.
Module address of
the PFQ module.
Channel on selected
Module.
Example: if
measuring gallons
and if 100 pulses = 1
gallon, enter 100.
The output RATE is
calculated by
counting number of
pulses per Sample
Time and scaling it to
EU/Time Period.
Sample Time is a
rolling window of
time (updated each
scan cycle) used to
count pulses. The
longer the Sample
Time the smoother
the rate output and
the longer it will take
to change; the
smaller the Sample
Time the noisier the
rate output but the
quicker the
response.
Time unit used to
scale the rate from
pulses per Sample
Time to:
EU per Second, or
Value or Selection
Read Only. To change
block order, right-click on a
Function Block and select
Execution Order.
Enter a value: from 1 to 5.
Enter a value: from 1 to
12.
Enter a value: from 1 to 4
Enter 0-60 seconds using
0.5 sec. intervals.
Select Per Second, Per
Minute, Per Hour
Revision 11
2/07