Table 68 On/Off General Tab Configuration Parameters - Honeywell HC900 Reference Manual

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Function Blocks
ON/OFF Function Block
Properties Function
Block
Control
234

Table 68 ON/OFF General tab configuration parameters

Parameter
Index #
N/A
Order
N/A
Tag Name
N/A
Descriptor
N/A
Direction
N/A
SP Tracking
19
Hysteresis
HC900 Hybrid Control Designer Function Block Reference Guide
Parameter Description
Execution Order
16-character tag name
Block description
Control Action
Setpoint Tracking
Output Hysteresis
Value or Selection
Read Only. To change block
order, right-click on a Function
Block and select Execution
Order.
REVERSE - Proportional action
causes output to decrease as
process variable increases.
DIRECT - Proportional action
causes output to increase as
process variable increases.
NONE
TRACK PV - When control
mode is "manual", local setpoint
tracks process variable.
TRACK RSP - When setpoint is
remote setpoint, local setpoint
tracks remote setpoint.
0 % to 10 % of input span
Revision 11
2/07

Advertisement

Table of Contents