Function Blocks
SCB Scale and Bias Function Block
Configuration parameters
Properties Group
Scale Factor
Bias
Example
F igure 91 shows function block diagrams using a SCB function block.
H
334

Table 98 SCB configuration parameters

Parameter
Index #
0
1
Example 1
Scale Factor = 5
Bias = 1000

Figure 91 SCB function block examples

HC900 Hybrid Control Designer Function Block Reference Guide
Parameter Description
K - Multiplier (scaling) constant
Bias Constant - is used to
compensate the input for drift of
an input value due to
deterioration of a sensor, or
constant offset to an input.
Example 2
Scale Factor = 1
Bias = 460
Value or Selection
–99999 to 99999
–99999 to 99999
Revision 11
2/07