Digital Input Pulse Accumulation - Honeywell Experion 8 Series Technical Information

Table of Contents

Advertisement

Series 8 Controller and I/O Specification, S803-150-500
3.3.9.

Digital Input Pulse Accumulation

Function
The Digital Input Pulse Accumulation accepts 24VDC signals as discrete inputs. The first 16 channels can be
configured either as Digital Input or Pulse accumulation to support Pulse Accumulation and frequency measurement
on per channel basis.
Notable Features
Extensive internal diagnostics for data integrity
Optional redundancy
Internal / External field power selection
Galvanic isolation
Detailed Specification – Digital Input Pulse Accumulation (8C-PDIPA1)
Parameter
Input / Output Module
IOTA Modules
Input Channels
1
Galvanic Isolation (any input terminal
voltage referenced to common)
Isolation Technique
Voltage Rating
DI Power Voltage Range
Module current rating
Signal Type (Pulse Accumulation)
Minimum Pulse Width
Individual Channel SCAN Time
ON Sense Voltage/Current
OFF Sense Voltage/Current
Input Impedance
Absolute Delay Across Input Filter and
Isolation
Module Removal and Insertion
Under Power
Note 1 – Channels 1-16 can support Pulse accumulation on per channel basis and Channels 17-32 can be configured as DI
Note 2 – System to Field type isolation, option available only with external user supplied power
Version 1
Specification
8C-PDIPA1 - 24VDC Digital Input Pulse Accumulation, Coated
8C-TDILA1
8C-TDILB1
32
1000 VAC RMS
2
Optical (In IOM)
24 VDC
18 to 30 VDC (For user supplied field power )
105 mA
Accumulation Type (0-1KHz, for minimum 30% DUTY CYCLE devices)
300 uSec
300 uSec
13 VDC (min) or 3 mA (min)
5 VDC (max) or 1.2 mA (max)
4.2 K
5 ms ± 20%
Supported
Support Pulse Accumulation & frequency
measurement
Support mix of per channel Pulse accumulation
and DI
Non Redundant, Coated
Redundant, Coated
33
9"
12"
July 2017

Advertisement

Table of Contents
loading

Table of Contents