Table 97 Rtmr Configuration Parameters - Honeywell HC900 Reference Manual

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

RPRES = Remote Preset (0.0 – 99999.9)
If Time-up , RPRES represents Stop value in seconds
If Time -down , RPRES represents Start value in seconds
PREL = Preload (0.0 – 99999.9)
If Time-up , PREL represents Start value in seconds
If Time-down , PREL represents Start value in seconds
Outputs
TIME = Elapsed time (for TIM_DN input =OFF), Time Remaining (for TIM_DN input = ON)
OUT = Output (Digital) turned ON when Preset value is reached or time reaches 0, depending on TIMDN
input status
Block properties
Double click on the function block to access the function block properties dialog box.
Configuration parameters
Properties Group
Presets
Remote Preset
Use Preload
Revision 11
2/07

Table 97 RTMR configuration parameters

Parameter
Index #
0
Local
Preset
1
2
HC900 Hybrid Control Designer Function Block Reference Guide
RTMR Resettable Timer Function Block
Parameter Description
Local Preset
ON = use remote preset
YES = use external preload
rather than zero for starting or
stopping
NO = Use default (0 second)
Function Blocks
Value or Selection
Click Radio Button to
select
Enter a value in the field
1 to 99999
Click on radio button to
select
Click on radio button to
select
331