Lim Velocity Limiter Function Block - Honeywell HC900 Reference Manual

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Function Blocks
VLIM Velocity Limiter Function Block
VLIM Velocity Limiter Function Block
Description
The VLIM label stands for Velocity (Rate) Limiter.
This block is part of the Auxiliary category.
Function
Limits the rate at which an analog input value (X) can change, when a digital input signal (EN) is ON.
Individual rate of change limits are configured for an increasing and a decreasing X, respectively.
Separate digital status outputs indicate when High (H) or Low (L) rate limits are active.
If EN = OFF or system state = NEWSTART*, then:
OUT = X,
L = OFF,
H = OFF.
If EN = ON and OUT < X, then:
OUT moves toward X at Increasing RATE limit,
L = OFF,
H = ON until OUT = X.
If EN = ON and OUT > X, then:
OUT moves toward X at Decreasing RATE,
L = ON until OUT = X,
H = OFF.
* Newstart is the first scan cycle following the cold start of the controller.
Input
X = Analog Value (Primary Input)
EN = Enable Input command
Output
OUT = Rate Limited Input Value
H = High Rate alarm indication
L = Low Rate alarm indication
428
HC900 Hybrid Control Designer Function Block Reference Guide
Revision 11
2/07