Table 119 Tpsc Start/Restart Tab Configuration Parameter - Honeywell HC900 Reference Manual

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Modes and
Permitted
Setpoints
Mode
Permitted
Setpoint
Initial Mode
Setpoint for
Initial Mode
Power up
Mode
Power up
Setpoint
Power Up
Power Up
Out
Out
Failsafe Out
Initial
Use initial
Setpoint
LSP
Value
Initial LSP
Value
Revision 11
2/07

Table 119 TPSC Start/Restart tab configuration parameter

MAN 7
Mode permitted for the
initial start and power up
AUTO 8
mode.
LSP 9
Setpoint permitted for
the initial start and
RSP 10
power up mode.
N/A
Mode at NEWSTART
Newstart is the first
scan cycle following the
cold start of the
controller
N/A
Setpoint at NEWSTART
Newstart is the first
scan cycle following the
cold start of the
controller
N/A
Mode at power up
N/A
Setpoint at power up
N/A
Output at Power up
N/A
Failsafe Output Value
15
Use Initial Local
Setpoint
16
Initial Local Setpoint
Value
HC900 Hybrid Control Designer Function Block Reference Guide
TPSC (3POS) Function Block
Manual
Automatic
May select both, must select one.
Local Setpoint
Remote Setpoint
May select both, must select one.
Manual
Automatic
Select one
Local Setpoint
Remote Setpoint
Select one
Manual
Retain Last Mode
Same mode (auto or manual)
Select one
Local Setpoint
Retain Last LSP/RSP
Same Setpoint (LSP or RSP)
Select one
LAST OUT - Same as at power down.
FAILSAFE - Failsafe output value.
–5 % to 105 %
Click on radio button to select
Enter Initial Local Setpoint Value
Function Blocks
413