Table 18 Alt Sequence Tab Parameters - Honeywell HC900 Reference Manual

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Function Blocks
ALT Alternator Function Block
Direct Style selected
Sequence
Parameter
Number
Field
1
Maximum Outputs used
2
Edit Sequence Order
62
Rotary, FOFO, or Fixed Style selected

Table 18 ALT sequence tab parameters

Action
Use the scroll buttons in
the active field and
select the number of
outputs to be used.
Click on the "Edit
Sequence Order" button
to activate the
Sequence Order dialog
box.
Click, Drag, and release
any output to any order,
as shown to the left, to
select the sequence in
which the outputs will be
turned on.
Click "OK".
HC900 Hybrid Control Designer Function Block Reference Guide
Selections
1 to16
Selecting less than 16
Outputs will make the
unused Outputs in the
"Output Selection"
column = 0 after "OK"
is selected.
Sequence Order
May be changed by a
Default =
special message.
OUT1,
OUT2,
OUT3
:
:
OUT15,
OUT16.
Comments
Revision 11
2/07

Advertisement

Table of Contents
loading

Table of Contents