Properties
Function
Ranging
PV High range
PV Low
Range
Display
Decimal
Places
Units
DEV Bar
Range (EU)
Limiting
SP High Limit
SP Low limit
SP Rate Down
SP Rate Up
Revision 11
2/07

Table 71 ON/OFF Range/limit tab configuration parameters

Parameter
Index #
0
1
N/A
N/A
N/A
12
13
15
16
HC900 Hybrid Control Designer Function Block Reference Guide
Parameter Description
PV High Range Value
PV Low Range Value
Number of digits to display after
decimal point.
Text to display for EU
Deviation Bar Range on the
Operator Interface
Setpoint High Limit Value -
prevents the local and remote
setpoints from going above the
value set here.
Setpoint Low Limit Value -
prevents the local and remote
setpoints from going below the
value set here.
Setpoint Rate Down value - when
making a setpoint change, this is
the rate at which setpoint will
change from the original setpoint
down to the new one.
Setpoint Rate Up value - when
making a setpoint change, this is
the rate at which setpoint will
change from the original setpoint
up to the new one.
Function Blocks
ON/OFF Function Block
Value or Selection
–99999 to 99999
–99999 to 99999
0 to 5
6 characters
–99999 to 99999
–99999 to 99999
–99999 to 99999
0 (off) to 9999 (eu/min)
0 (off) to 9999 (eu/min)
239