Table 124 Tpsc Alarms Tab Configuration Parameters - Honeywell HC900 Reference Manual

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Properties Group
Parameter
Alarm 1
Setpoint 1
Type
Setpoint 2
Type
Alarm 2
Setpoint 1
Type
Setpoint 2
Type
%
Alarm
Hysteresis
Revision 11
2/07

Table 124 TPSC Alarms tab configuration parameters

Index #
Parameter Description
22
Alarm 1 Setpoint 1 Value
- this is the value at which
you want the alarm type
chose below to activate
N/A
Alarm 1 Setpoint 1 Type -
select what you want
Alarm 1 Setpoint 1 to
represent.
23
Alarm 1 Setpoint 2 Value
N/A
Alarm 1 Setpoint 2 Type
24
Alarm 2 Setpoint 1 Value
N/A
Alarm 2 Setpoint 1 Type
25
Alarm 2 Setpoint 2 Value
N/A
Alarm 2 Setpoint 2 Type
30
Alarm Hysteresis in %
HC900 Hybrid Control Designer Function Block Reference Guide
Function Blocks
TPSC (3POS) Function Block
Value or Selection
–99999 to 99999 in Engineering
Units
Within the PV range when alarm
type is PV or SP
Within PV span when alarm type
is DEV
–5 % to 105 % when alarm type is
output.
Selections:
NO ALARM
PV_HIGH
High PV Alarm
PV_LOW
Low PV Alarm
DEV_HIGH
High Deviation
alarm
DEV_LOW
Low Deviation
alarm
SP_HIGH
High Setpoint
alarm
SP_LOW
Low Setpoint
alarm
OUT_HIGH
High Output
alarm
OUT_LOW
Low Output
alarm
Same as Alarm 1 Setpoint 1
Same as Alarm 1 Setpoint 1
Same as Alarm 1 Setpoint 1
Same as Alarm 1 Setpoint 1
Same as Alarm 1 Setpoint 1
Same as Alarm 1 Setpoint 1
0 % to 5 %
421