MMA Min/Max/Avg Function Block
Double click on the function block to access the function block properties dialog box.
Configuration parameters

Table 64 Min/Max/Ave/Sum function block configuration parameters

Properties Group
Set Calculation
Inputs Used
Parameters
Standard
Deviations
214
Parameter
Index #
N/A
1
HC900 Hybrid Control Designer Function Block Reference Guide
Parameter Description
Number of inputs connected to
block
(Connect inputs in numerical
order; that is, unused inputs from
the bottom up - X6, X5, etc.)
Unused inputs default to 0.
Number of standard deviations
within which inputs are used for
calculation
Value or Selection
1 to 6
–99999 to 99999
<0 No Standard
Deviation
=0 Standard Deviation
with no alarm
>0 Standard Deviation
with alarm
Revision 11
2/07