Configurable Parameters
Properties Group
Block
Order
Address
Rack
Module
Channel
Frequency Span
Set High
Input (Hz)
Set Low
Input (Hz)
Output Range in
High (EU)
EU
Low (EU)
Bias
Settings
Pulse Width
(Range)
Filter Time
(sec)
Failsafe
Use Value
Up scale
Down scale
HOLD
Revision 11
2/07

Table 48 Frequency Input configuration parameters

Parameter
Index #
N/A
0
0
0
7
8
5
6
2
9
1
3
4
4
4
HC900 Hybrid Control Designer Function Block Reference Guide
Parameter Description
Execution Order for Block
This is the rack address of the PFQ
module.
Module address of the PFQ module.
Channel on selected Module.
High frequency value of the input
device. Exceeding this limit causes an
over-range error.
Low frequency value of the input
device. Exceeding this limit causes an
under -range error.
High range value. Frequency span in
Hz is scaled to the output range in
EU.
Low range value. Frequency span in
Hz is scaled to the output range in
EU.
Bias value added to the output.
The input signal is rejected if it is
below this pulse width. The frequency
of pulses above this width must be in
this frequency range; otherwise the
output goes to failsafe and a failure-
to-convert error occurs.
Filter time constant in seconds.
When FAIL is ON output is set to this
value.
When FAIL is ON output is set to
Upper Range Limit.
When FAIL is ON output is set to
Lower Range Limit.
When FAIL is ON output is held.
Function Blocks
FI Frequency Input
Value or Selection
Read Only. To
change block order,
right-click on a
Function Block and
select Execution
Order.
Enter a value:
from 1 to 5.
Enter a value:
from 1 to 12.
Enter a value:
from 1 to 4
Enter value in Hz.
Enter value in Hz.
Enter value in EU.
Enter value in EU.
Enter value in EU.
500µsec (10Hz-
500Hz)
50µsec (10Hz-5KHz)
2.5µsec (10Hz-
100KHz)
Enter value in
seconds.
Click to select, enter
a value.
Click to select.
Click to select.
Click to select.
161

Advertisement

Table of Contents
loading

Table of Contents