Honeywell HC900 Reference Manual page 220

Hybrid control designer
Hide thumbs Also See for HC900:
Table of Contents

Advertisement

Function Blocks
MBW Modbus Write Function Block
Sequence
Parameter
Number
Field
3
4
5
You must press [APPLY] to accept the register changes.
6
206
Action
Type in the address of
the register (in Hex) on
the slave device
From the drop down
menu, select the
Register Data Type
The function code for
"Unsigned 16 or
Signed 16 register data
type is (06)*
The function code for
"Float, Unsigned 32 or
Signed 32 register data
type is (10 hex)*
*automatically selected
when you select
"Register Data Type"
HC900 Hybrid Control Designer Function Block Reference Guide
Selections
Float
Several standard
Modbus RTU function
Unsigned 32
codes are supported.
These standard
Signed 32
function codes provide
basic support for IEEE
Unsigned 16
32-bit floating point
numbers and 16-bit
Signed 16
integer register
representation of
instrument's process
data. (see Sequence
Number 5 below)
Preset Single
Function code 06
Registers –
presets integer value
Function Code
into a single register.
06
Function Code 10 hex
Preset Multiple
presets values into
Registers –
holding registers.
Function Code
NOTE: Refer to the
10 hex
Communications
manual for the function
codes supported by the
specific device.
Comments
Revision 11
2/07