CONFIGURATION AND CONTROL PARAMETERS

Config. Par.
No. Name
C.01 DIR/REVY1 Selects the output action of Y1 to adapt the valve or damper direction
Dir
Rev
C.05 CPATYP
Selects the Control Point /SetPoint Adjustment type
0
1
2
C.06 YRange
Selects the output control range
0
1
C.12 X2ext
Enable / Disables the X1 sensor input to be used for both X1 and X2 inputs
0
1
2
C.13 LimTyp
Limitation type determines whether the limit function is low or high.
0
1
C.14 Senstyp
Sensor type determines automatic detection or manual selection of
NTC sensor type
0
1
C.15 Y1CTRF
Control function
0
1
1)
C.22 Adr
Sets the serial communication address, used for service or maintenance.
0
255
C.23 DefProg
Initiates the default programming.
0
1
C.24
Start point (0%) of X1 and X2 span adjustment
UStartPoint
0
10V
C.25 UEndPoint End point (100%) of X1 and X2 span adjustment
0
10V
C.26 OffDelay
Off delay for On/Off output
0
60min
1)
actual value will not be changed during reset to default parameter
For detailed information of configuration parameters see chapter Configuration Settings.
Direct acting output signal
Reverse acting output signal
Potentiometer
CPA/SPA
range
range
internal
CPA: ±10%
CPA: ±10%
100kΩ...0Ω
100kΩ...0Ω
SPA: 0...100%
2 ... 10Vdc
0 ... 10Vdc
X2 installed
X1 signal used for X2
X2 disabled
Low limit
High limit
Auto detection T3
NTC sensor type T3
Direct control behaviour
Reverse control behaviour
Min.
Max.
No Defaultprogramming
Initiates Defaultprogramming
Min.
Max. (resolution 0.1V)
Min.
Max. (resolution 0.1V)
Min.
Max. (resolution 1min)
Table 3. Configuration Parameters R7426D
Description
Sensor / Remote Setpoint Unit
Type Numbers
internal
43193982-001
43193982-001
3
R7426D UNIVERSAL INPUT CONTROLLER
Default Setting Actual Value
Dir
0
1
0
1
0
1
254
0
0
10
0
EN1B-0204GE51 R0403