13 TROUBLESHOOTING
13.2 List of errors
Error
code
Error name
(DEC.)
000
Normal status
100
Faults
101
QD70D not prepared
102
Stop signal ON at start
103
Software stroke limit +
104
Software stroke limit -
Programmable controller
105
READY OFF during
Programmable controller
110
READY OFF during writing
13 - 3
The following table shows the error details and remedies to be taken when an error
occurs.
Hardware is faulty.
Start was made when the QD70D was not ready.
A start request was given when the axis stop signal
(Y(n+1)0 to Y(n+1)7) is ON.
• Positioning control was carried out in a position in
excess of " Pr. 1 Software stroke limit upper limit
value".
• " Md. 1 Current feed value" or " Da. 6 Positioning
address/movement amount" (New current value) has
exceeded " Pr. 1 Software stroke limit upper limit
value".
• Positioning control was carried out in a position in
excess of " Pr. 2 Software stroke limit lower limit
value".
• " Md. 1 Current feed value" or " Da. 6 Positioning
address/movement amount" (New current value) has
exceeded " Pr. 2 Software stroke limit lower limit
value".
The Programmable controller READY signal (Yn0)
turned OFF during operation.
The Programmable controller READY signal (Yn0)
turned OFF immediately after turning ON.
Error
—
MELSEC-Q
Operation status at error occurrence
—
The system stops
Start is not made.
At start: Start is not made.
At current value changing analysis:
Current value changing is not made.
During operation:
• During speed control (including speed
control of speed-position switching control)
or JOG operation, the axis decelerates to a
stop as soon as " Md. 1 Current feed value"
exceeds the software stroke limit range.
• During position control (including position
control of speed-position switching control),
the axis decelerates to a stop as soon as
" Md. 1 Current feed value" or " Da. 6
Positioning address/movement amount"
exceeds the software stroke limit range.
The axis decelerates to a stop.
—
13 - 3