Mitsubishi Electric QD70D4 User Manual page 173

Q series
Table of Contents

Advertisement

8 OPR CONTROL
8 - 15
Restrictions
A pulse generator with a zero signal is required.
When using a pulse generator without a zero signal, generate a zero signal using an
external signal.
Precaution during operation
(1) If " OPR. 8 Setting for the movement amount after near-point dog ON" is less
than the deceleration distance from "OPR. 4 OPR speed" to "OPR. 5 Creep
speed", machine OPR control is completed normally.
(2) When the near-point dog is ON at start, an error, "Start during near-point dog
ON" (Error code: 201) occurs. Perform JOG operation to move the axis to the
position where the near-point dog turns OFF.
Refer to Section 8.4 OPR retry function.
(3) If the axis stop signal is turned ON during operation performed at "OPR. 4
OPR speed", the axis decelerates to a stop at the time set in "OPR. 7 DEC/
STOP time at OPR".
MELSEC-Q
8 - 15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qd70d8

Table of Contents