3 SPECIFICATIONS AND FUNCTIONS
3.3.2 Details of input signal (QD70D
Device
Signal name
No.
Xn0
Module READY
Xn1
Axis error
occurrence
Xn2
Axis warning
occurrence
Xn8
Axis 1
BUSY *1
Xn9
Axis 2
XnA
Axis 3
XnB
Axis 4
XnC
Axis 5
XnD
Axis 6
XnE
Axis 7
XnF
Axis 8
X(n+1)0
Axis 1
Start
complete
X(n+1)1
Axis 2
X(n+1)2
Axis 3
X(n+1)3
Axis 4
X(n+1)4
Axis 5
X(n+1)5
Axis 6
X(n+1)6
Axis 7
X(n+1)7
Axis 8
X(n+1)8
Axis 1
Positioning
complete* 2
X(n+1)9
Axis 2
X(n+1)A
Axis 3
X(n+1)B
Axis 4
X(n+1)C
Axis 5
X(n+1)D
Axis 6
X(n+1)E
Axis 7
X(n+1)F
Axis 8
Important
*1 : The BUSY signal turns ON even when position control of movement amount 0 is
executed. However, since the ON time is short, the ON status may not be detected in the
sequence program.
*2 : "Position control complete" of the QD70D refers to the point when the pulse output from
QD70D is completed.
Thus, even if the QD70D's positioning complete signal turns ON, the system may continue
operation.
3 - 5
The ON/OFF timing and conditions of the input signals are shown below.
ON: Prepared
• When the Programmable controller READY signal [Yn0] turns from OFF to ON, the
OFF: Not
parameter and the OPR data setting range is checked. If no error is found, this signal
prepared
turns ON. (When the axis error occurrence signal [Xn1] is ON, this signal does not
watch dog
turn ON if the Programmable controller READY signal [Yn0] is turned from OFF to
timer error
ON.)
• When the Programmable controller READY signal [Yn0] turns OFF, this signal turns
OFF.
• When a watch dog timer (WDT) error occurs, this signal turns OFF.
• This signal is used for interlock in a sequence program, etc.
Module READY signal [Xn0]
• This signal turns ON if an error occurs in any of axes 1 to 8, and turns OFF when
OFF: No error
ON: Error
" Cd. 1 Axis error reset" is set for all axes.
occurrence
(Use " Md. 10 Error status" to confirm the error status of the corresponding axis.)
• This signal turns ON if a warning occurs in any of axes 1 to 8, and turns OFF when
OFF: No warning
ON: Warning
" Cd. 1 Axis error reset" is set for all axes.
occurrence
(Use " Md. 11 Warning status" to confirm the warning status of the corresponding
axis.)
OFF: Not BUSY
• This signal turns ON at the start of positioning control, OPR control or JOG operation.
ON: BUSY
It turns OFF when the " Da. 7 Dwell time" has passed after positioning control stops.
(This signal remains ON during positioning control.)
• This signal turns OFF at error or stop.
OFF: Start
• This signal turns ON when the positioning start signal turns ON and the QD70D
incomplete
starts the positioning control process.
ON: Start
(The start complete signal also turns ON during OPR control.)
complete
Start complete signal [X(n+1)0]
OFF: Positioning
• This signal turns ON for the time set in " Pr. 7 Positioning complete signal output
incomplete
time" from completion of position control of the corresponding axis.
ON: Positioning
(It does not turn ON if 0 is set in " Pr. 7 Positioning complete signal output time".)
complete
• While ON, this signal turns OFF if a positioning control start (including OPR control)
or JOG operation start is made.
• This signal does not turn ON at the termination of JOG operation.
• This signal does not turn ON if position control is stopped midway.
Programmable controller CPU)
Programmable controller
READY signal [Yn0]
Positioning start signal [Yn8]
Description
ON
OFF
ON
OFF
ON
OFF
ON
OFF
MELSEC-Q
3 - 5