5.3 Input/Output Combined Modules

5.3.1 Input/output combined module specifications

Model
Input Type
Dynamic
A42XY
scan
DC
input
AH42
(sink type)
Output
Model
Type
Dynamic
A42XY
scan
Transistor
AH42
output
(sink type)
Number
Isolation
of Points/
Method
Module
64 points
Photocoupler
*1
insulation
32 points
No. of
Rated
Points/
Load
Module
Voltage
64 points
12/24VDC
32 points
Rated
Input
Input
Current
Voltage
12/24VDC
3/7mA
Max. Load Current
Per
Per Point
Common
50mA
0.1A
1A
78
Operating Voltage
ON
OFF
Voltage
Voltage
7VDC
or
3VDC
or
higher
lower
9.5VDC or
6VDC
or
higher
lower
Input Response Time
OFF to
ON to
ON
OFF
16msec or
16msec or
less
less
2msec or
2msec or
less
less