Table 6.2 Error Code List for AnACPU (Continue)
Error
Error
Code
Massage
(D9008)
"LINK
47
PARA.
ERROR"
"OPERATI
50
ON
ERROR"
(Checked
at
execution
of
instruction.)
Detailed
Error
CPU
Code
States
(D9091)
Continu
(1) Data written to the
e
(2) Total number of
501
Stop or
(1) When file registers
Continu
e (set
by
parame
ter)
(2) File registers are
502
Combination of the
devices specified by
instruction is incorrect.
503
Stored data or constant
of specified device is
not in the usable range.
504
Set number of data to
be handled is out of the
usable range.
107
Error and Cause
parameter areas of
the link of which
range was set by
parameters using a
peripheral device
does not conform
with the data of link
parameters read by
the CPU.
Or, link parameters
are not written.
local stations is set
at 0.
(R) are used,
operation is
executed outside of
specified ranges of
device numbers and
block numbers of
file registers (R).
used in the program
without setting
capacity of file
registers.
Corrective Action
(1) Write in parameters
again and check.
(2) Check setting of
station numbers.
(3) If the same error
indication is given
again, it is hardware
failure.
Consult
Mitsubishi
representative.
Read the error step
using a peripheral
device and check and
correct program of the
step.