Download  Print this page

Advertisement

Table 6.3 Error Code List for AnUCPU (Continue)
Error
Error
Code
Massage
(D9008)
"PARAMET
11
ER
ERROR"
(Checked
at power on
and at
STOP/PAU
SE →
RUN.)
Detailed
Error
CPU
Code
States
(D9091)
111
STOP
Capacity settings of the
main and sub
programs,
microcomputer
program, file register
comments, status latch,
sampling trace and
extension file registers
are not within the
usable range of the
CPU.
112
Total of the set
capacity of the main
and sub programs, file
register comments,
status latch, sampling
trace and extension file
registers exceeds
capacity of the memory
cassette.
113
Latch range set by
parameters or setting
of M, L or S is
incorrect.
114
Sum check error
115
Either of settings of the
remote RUN/
PAUSE contact point
by parameters,
operation mode at
occurrence of error,
annunciator indication
mode, or STOP →
RUN indication mode
is incorrect.
116
The MNET-MINI
automatic refresh
setting by parameters
is incorrect.
117
Timer setting by
parameters is
incorrect.
118
Counter setting by
parameters is
incorrect.
113
Error and Cause
Corrective Action
Read parameters in the
CPU memory, check the
contents, make
necessary corrections
and write them again to
the memory.