Table 6.3 Error Code List for AnUCPU (Continue)
Error
Error
Code
Massage
(D9008)
"CAN'T
13
EXECUTE
(P)"
(Checked
at
execution
of
instruction.)
Detailed
Error
CPU
Code
States
(D9091)
131
STOP
The same device
number is used at two
or more steps for the
pointers (P) and
interrupt pointers (I)
used as labels to be
specified at the head of
jump destination.
132
Label of the pointer (P)
specified in the
instruction is not
provided before the
133
(1) The
(2) The
115
Error and Cause
CJ ,
SCJ ,
CALL ,
CALLP ,
JMP ,
or
LEDA/B FCALL
LEDA/B BREAK
END
instruction.
RET
instruction was
included in the
program and
executed though
the
CALL
instruction
was not given.
NEXT
LEDA/B BREAK
instructions were
included in the
program and
executed though
the
FOR
instruction
was not given.
Corrective Action
Eliminate the same
pointer numbers
provided at the head of
jump destination.
Read the error step
using a peripheral
device, check contents
and insert a jump
destination pointer (P).
(1) Read the error step
using a peripheral
device, check
contents and correct
program of the step.
(2) Reduce the number
of nesting levels of
the
CALL ,
CALLP
and
FOR
instructions
to 5 or less.