Table 6.1 Error Code List for AnNCPU (Continue)
Error
Error
Code
Message
(D9008)
"CAN'T
13
EXECUTE(P)
" (Checked at
the
execution of
instruction)
CPU
Error and Cause
States
Stop
(5) The number of the
FOR
instructions is
different from that of the
NEXT
(6) A
JMP
given within a
FOR to NEXT
causing the processing
to exit the loop.
(7) Processing exited
subroutine by the
JMP
instruction
before execution of the
RET
instruction.
(8) Processing jumped into
a step in a
FOR to NEXT
or into a subroutine by
the
JMP instruction.
(9) The
STOP
instruction is given in an
interrupt program, a
subroutine program or in
a
FOR to NEXT
85
Corrective Action
Read the error step by use
of peripheral equipment and
correct the program at that
step.
instructions.
(Insert a jump destination or
reduce multiple destinations
instruction is
to one.
loop
loop
loop.