Table 6.3 Error Code List for AnUCPU (Continue)
Error
Error
Code
Massage
(D9008)
"LINK
47
PARA.
ERROR"
Detailed
Error
CPU
Code
States
(D9091)
475*
Continu
[When using
e
MELSECNET/10]
(1) The contents of the
(2) The link parameters
(3) The setting for the
476*
[When using
MELSECNET/10]
(1) The contents of the
(2) The link parameters
(3) The setting for the
477
A ink parameter error
was detected by the
CC-Link module.
130
Error and Cause
network parameters
for the third link unit,
written from a
peripheral device,
differ from the actual
network system.
for the third link unit
have not been
written.
total number of
stations is 0.
network parameters
for the fourth link
unit, written from a
peripheral device,
differ from the actual
network system.
for the fourth link unit
have not been
written.
total number of
stations is 0.
Corrective Action
(1) Write the parameters
again and check.
(2) Check the station
number settings.
(3) Persistent error
occurrence may
indicate a hardware
fault. Consult your
nearest Mitsubishi
representative,
explaining the nature
of the problem.
(1) Write the parameters
in again and check.
(2) If the error appears
again, there is a
problem with the
hardware.
Consult your nearest
System Service, sales
office or branch office.