Table 6.3 Error Code List for AnUCPU (Continue)
Error
Error
Code
Massage
(D9008)
"CHK
14
FORMAT
ERR"
(Checked
at
STOP/PAU
SE →
RUN.)
Detailed
Error
CPU
Code
States
(D9091)
141
STOP
142
143
144
145
146
147
Error and Cause
Instructions (including
NOP ) other than
LDX ,
LDIX ,
ANDX
and
ANIX
are included
in the
CHK
instruction
circuit block.
Multiple
CHK
instructions are given.
The number of contact
points in the
CHK
instruction circuit block
exceeds 150.
The
LEDA CHK
instructions are not
paired with the
LEDA CHKEND
instructions, or 2 or
more pairs of them are
given.
Format of the block
shown below, which is
provided before the
CHK
instruction
circuit block, is not as
specified.
P254
CJ P
Device number of D1
in the
CHK D1 D2
instruction is different
from that of the contact
point before the
CJ P
instruction.
Index qualification is
used in the check
pattern circuit.
117
Corrective Action
Check the program of
the
CHK
instruction and
correct it referring to
contents of detailed
error codes.