Table 6.3 Error Code List for AnUCPU (Continue)
Error
Error
Code
Massage
(D9008)
"FUSE
32
BREAK
OFF"
(Checked
continuousl
y.)
Detailed
Error
CPU
Code
States
(D9091)
Stop or
(1) There is an output
Continu
e (set
by
(2) The external power
parame
ter)
Error and Cause
module of which
fuse is blown.
supply for output
load is turned OFF
or is not connected.
122
Corrective Action
(1) Check the FUSE
BLOWN indicator
LED on the output
module and replace
the fuse.
(2) Read detailed error
code using a
peripheral device and
replace the fuse of
the output module
which corresponds to
the data (I/O head
number).
Or, monitor special
registers D9100 to
D9107 using a
peripheral device and
replace the fuse of
the output module of
which corresponding
data bit is "1".
(3) Check the ON/OFF
status of the external
power supply for
output load.