Table 6.3 Error Code List for AnUCPU (Continue)
Error
Error
Code
Massage
(D9008)
"OPERATI
50
ON
ERROR"
(Checked
at
execution
of
instruction.)
Detailed
CPU
Error
Code
States
(D9091)
501
Stop or
(1) When file registers
Continu
e (set
by
parame
ter)
(2) File registers are
502
Combination of the
devices specified by
instruction is incorrect.
503
Stored data or constant
of specified device is
not in the usable range.
504
Set number of data to
be handled is out of the
usable range.
505
(1) Station number
(2) Head I/O number
131
Error and Cause
(R) are used,
operation is
executed outside of
specified ranges of
device numbers and
block numbers of
file registers (R).
used in the program
without setting
capacity of file
registers.
specified by the
LEDA/B LRDP
,
LEDA/B LWTP
LRDP ,
LWTP
instructions is not a
local station.
specified by the
LEDA/B RFRP
,
LEDA/B RTOP
RFRP ,
RTOP
instructions is not of
a remote station.
Corrective Action
Read the error step
using a peripheral
device and check and
correct program of the
step.