Download  Print this page

Advertisement

(5) Setting
For A61P, A61PEU, A62P, A62PEU, A65P or A66P, the input voltage
range, 100V or 200V, must be specified by placing a jumper (supplied)
across two terminals as described below:
Remove the terminal cover from
the power supply module.
Remove the pair of terminal
screw, (2) or (3), according to the
supply voltage range (1) used.
(2): For the 100 VAC range.
(3): For the 200 VAC range.
Fit the jumper (4) and secure it
with the terminal screw.
Fit the jumper in the direction
shown in the figure at right.
(The figure at right shows an
example when the supply line
voltage is 100 VAC.)
POINT
If the setting differs from the supply line voltage, the following occurs: do not
mis-set.
Setting to 100VAC
(jumper fitted as indicated at (2))
Setting to 200VAC
(jumper fitted as indicated at (3))
No setting
(jumper not fitted)
(1)
(4)
(2)
(3)
Supply Line Voltage
100VAC
No error occurs in the
module. However, the
CPU does not
operate.
No error occurs in the module.
However, the CPU does not operate.
38
200VAC
The power supply
module is damaged.
(The CPU is not
damaged.)