VeriCase User Guide
Rosemount 3308 and 5300 Series Level
®
®
Transmitters with HART
and Modbus

Advertisement

loading
Need help?

Need help?

Do you have a question about the Rosemount HART Modbus VeriCase 3308 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount HART Modbus VeriCase 3308 Series

  • Page 1 Quick Start Guide 00825-0500-4530, Rev AD April 2019 ™ Rosemount VeriCase User Guide Rosemount 3308 and 5300 Series Level ® ® Transmitters with HART and Modbus...
  • Page 2: Table Of Contents

    Quick Start Guide April 2019 Contents Overview............................3 Check contents and verification sheet..................4 Verify the Rosemount 3308 transmitter..................6 Verify the Rosemount 5300 transmitter..................10 Generate a report........................13 FAQs............................14 Rosemount VeriCase...
  • Page 3: Overview

    April 2019 Quick Start Guide Overview ™ The Rosemount VeriCase is a mobile verification tool for the Rosemount ® ® 3308 and 5300 Level Transmitters with HART and Modbus communications. The Rosemount VeriCase accuracy is within ±1 mm. Figure 1-1 identifies the parts inside the case that you should be familiar with before performing verification.
  • Page 4: Check Contents And Verification Sheet

    Quick Start Guide April 2019 Check contents and verification sheet Check contents Procedure Open the Rosemount VeriCase and check that it contains the following items: • USB stick containing • User Instructions ® ® • Microsoft Excel workbook • Calibration certificate •...
  • Page 5 April 2019 Quick Start Guide Power up the Rosemount VeriCase The Rosemount VeriCase can be powered by either a 110V/220V power supply or a 12VDC power adapter supplied with the Rosemount VeriCase. To power up the Rosemount VeriCase and connect it to a transmitter head: Procedure 1.
  • Page 6: Verify The Rosemount 3308 Transmitter

    Quick Start Guide April 2019 Verify the Rosemount 3308 transmitter Prerequisites 1. Fill in the details in the Verification Data tab of the Excel workbook. Record the serial number of the device from the nameplate of the transmitter. 2. (Optional) Select the Imperial Units check box to enter data in inches and Fahrenheit.
  • Page 7 April 2019 Quick Start Guide 3. Make sure the cable switch on the Rosemount VeriCase is set to position 1. 4. Select Service Tools → Routine Maintenance, and then select Verification. 5. In the Verification window, select Next. 6. Enter the Distance and the Electronics Temperature, displayed on the Verification window, to the Excel workbook.
  • Page 8 Quick Start Guide April 2019 7. Enter the VeriCase temperature, displayed on the device, to the Excel workbook. 8. Switch to the next cable on the Rosemount VeriCase, and then select Next. 9. Repeat Step 6-Step 8 for all six cable lengths. 10.
  • Page 9 April 2019 Quick Start Guide 11. After the configuration is restored, disconnect communication to the transmitter. Quick Start Guide...
  • Page 10: Verify The Rosemount 5300 Transmitter

    Quick Start Guide April 2019 Verify the Rosemount 5300 transmitter Prerequisites Open the Rosemount Radar Master and record the serial number and firmware revision of the device to be tested in the Verification data tab of the workbook. This information can be found in the Device Properties window in the Device menu in Rosemount Radar Master.
  • Page 11 April 2019 Quick Start Guide c) Make sure that the below parameters are set with the following values: • Propagation Factor: 1,000 • Tank Connection Length: 0 • Remote housing: None • Probe angle: 0 • Vapor DC: 1 • Measurement mode: Liquid product level, solid product level or product level and interface level d) Save these configuration changes and restart the device.
  • Page 12 Quick Start Guide April 2019 Postrequisites Once the verification is complete, restore the original configuration by uploading the backup file to the transmitter. Upload backup file to transmitter Procedure 1. Select Device → Upload Config from File… and reload the saved file. 2.
  • Page 13: Generate A Report

    April 2019 Quick Start Guide Generate a report Once testing is complete, a report can be generated from the Excel workbook. It is possible to generate a verification report and/or a Q4 certificate. Prerequisites To generate a Q4 certificate, the analog output of the transmitter under verification should be tested at 4 mA, 12 mA and 20 mA and the results should be saved in the Q4 Data tab before generating the certificate.
  • Page 14: Faqs

    Quick Start Guide April 2019 FAQs ™ Q: Can verification of a F Fieldbus transmitter be performed OUNDATION using the Rosemount VeriCase? A: Yes, but an external FOUNDATION Fieldbus modem (and power supply if explosion-proof) is required as the FOUNDATION Fieldbus modem is not built into the Rosemount VeriCase.
  • Page 15 April 2019 Quick Start Guide Quick Start Guide...
  • Page 16 The Emerson logo is a Twitter.com/Rosemount_News trademark and service mark of Emerson Electric Facebook.com/Rosemount Co. Rosemount is mark of one of the Emerson Youtube.com/user/ family of companies. All other marks are the RosemountMeasurement property of their respective owners.

This manual is also suitable for:

Rosemount hart modbus vericase 5300 series