5.2 PRODUCT SETUP
!
PATH: SETTINGS
PRODUCT SETUP
# USER-PROGRAMMABLE
# LEDS
# TRIP & ALARM
# LEDS
# USER-PROGRAMMABLE
# LED 1
# USER-PROGRAMMABLE
# LED 2
5
# USER-PROGRAMMABLE
# LED 48
The TRIP and ALARM LEDs are on LED panel 1. Each indicator can be programmed to become illuminated when the
selected FlexLogic™ operand is in the logic 1 state. There are 48 amber LEDs across the relay faceplate LED panels. Each
of these indicators can be programmed to illuminate when the selected FlexLogic™ operand is in the logic 1 state.
LEDs 1 through 24 inclusive are on LED panel 2; LEDs 25 through 48 inclusive are on LED panel 3.
Refer to the LED INDICATORS section in the HUMAN INTERFACES chapter for the locations of these indexed LEDs. This
menu selects the operands to control these LEDs. Support for applying user-customized labels to these LEDs is provided.
If the
setting is "Self-Reset" (default setting), the LED illumination will track the state of the selected LED oper-
LED X TYPE
and. If the
LED X TYPE
remote device via a communications channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5–4: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
LED 1 Operand
LED 2 Operand
LED 3 Operand
LED 4 Operand
LED 5 Operand
LED 6 Operand
LED 7 Operand
LED 8 Operand
LED 9 Operand
LED 10 Operand
LED 11 Operand
LED 12 Operand
Refer to the CONTROL OF SETTINGS GROUPS example in the CONTROL ELEMENTS section for group activation.
5-20
!"

USER-PROGRAMMABLE LEDS

TRIP LED INPUT:
OFF
ALARM LED INPUT:
OFF
LED 1 OPERAND:
Off
LED 1 TYPE:
Self-Reset
setting is 'Latched', the LED, once lit, remains so until reset by the faceplate RESET button, from a
PARAMETER
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
SETTING GROUP ACT 7
SETTING GROUP ACT 8
BREAKER 1 OPEN
BREAKER 1 CLOSED
BREAKER 1 TROUBLE
Off
C60 Breaker Management Relay
5.2.10 USER-PROGRAMMABLE LEDS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Self-Reset, Latched
SETTING
PARAMETER
LED 13 Operand
Off
LED 14 Operand
BREAKER 2 OPEN
LED 15 Operand
BREAKER 2 CLOSED
LED 16 Operand
BREAKER 2 TROUBLE
LED 17 Operand
SYNC 1 SYNC OP
LED 18 Operand
SYNC 2 SYNC OP
LED 19 Operand
Off
LED 20 Operand
Off
LED 21 Operand
AR ENABLED
LED 22 Operand
AR DISABLED
LED 23 Operand
AR RIP
LED 24 Operand
AR LO
5 SETTINGS
GE Multilin