5 SETTINGS
Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 2 of 3)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
FLEXELEMENT 1 PKP
FlexElements™
FLEXELEMENT 1 OP
FLEXELEMENT 1 DPO
FLEXELEMENT 8 PKP
FLEXELEMENT 8 OP
FLEXELEMENT 8 DPO
ELEMENT:
PHASE UV1 PKP
Phase UV
PHASE UV1 OP
PHASE UV1 DPO
PHASE UV1 PKP A
PHASE UV1 PKP B
PHASE UV1 PKP C
PHASE UV1 OP A
PHASE UV1 OP B
PHASE UV1 OP C
PHASE UV1 DPO A
PHASE UV1 DPO B
PHASE UV1 DPO C
PHASE UV2
ELEMENT:
SETTING GROUP ACT 1
Setting Group
SETTING GROUP ACT 8
ELEMENT:
SYNC 1 DEAD S OP
Synchrocheck
SYNC 1 DEAD S DPO
SYNC 1 SYNC OP
SYNC 1 SYNC DPO
SYNC 1 CLS OP
SYNC 1 CLS DPO
SYNC 2
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1
Contact Inputs
Cont Ip 2
Cont Ip 1
Cont Ip 2
INPUTS/OUTPUTS:
Cont Op 1
Contact Outputs,
Cont Op 2
Current
(from detector on
Cont Op 1
Form-A output only)
Cont Op 2
INPUTS/OUTPUTS:
Cont Op 1
Contact Outputs,
Cont Op 2
Voltage
(from detector on
Cont Op 1
Form-A output only)
Cont Op 2
INPUTS/OUTPUTS:
REMOTE INPUT 1 On
Remote Inputs
REMOTE INPUT 32 On
INPUTS/OUTPUTS:
Virt Ip 1
Virtual Inputs
Virt Ip 32
INPUTS/OUTPUTS:
Virt Op 1
Virtual Outputs
Virt Op 64
REMOTE DEVICES
REMOTE DEVICE 1 On
REMOTE DEVICE 16 On
REMOTE DEVICE 1 Off
REMOTE DEVICE 16 Off
GE Multilin
OPERAND DESCRIPTION
FlexElement 1 has picked up
FlexElement 1 has operated
FlexElement 1 has dropped out
FlexElement 8 has picked up
FlexElement 8 has operated
FlexElement 8 has dropped out
At least one phase of UV1 has picked up
At least one phase of UV1 has operated
At least one phase of UV1 has dropped out
Phase A of UV1 has picked up
Phase B of UV1 has picked up
Phase C of UV1 has picked up
Phase A of UV1 has operated
Phase B of UV1 has operated
Phase C of UV1 has operated
Phase A of UV1 has dropped out
Phase B of UV1 has dropped out
Phase C of UV1 has dropped out
Same set of operands as shown for PHASE UV1
Setting group 1 is active
Setting group 8 is active
Synchrocheck 1 dead source has operated
Synchrocheck 1 dead source has dropped out
Synchrocheck 1 in synchronization has operated
Synchrocheck 1 in synchronization has dropped out
Synchrocheck 1 close has operated
Synchrocheck 1 close has dropped out
Same set of operands as shown for SYNC 1
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
On
(will not appear unless ordered)
On
(will not appear unless ordered)
Off
(will not appear unless ordered)
Off
(will not appear unless ordered)
IOn
(will not appear unless ordered)
IOn
(will not appear unless ordered)
IOff
(will not appear unless ordered)
IOff
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
VOff
(will not appear unless ordered)
VOff
(will not appear unless ordered)
Flag is set, logic=1
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
C60 Breaker Management Relay
5.4 FLEXLOGIC™