5 SETTINGS
Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 2 of 3)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
FLEXELEMENT 1 PKP
FlexElements™
FLEXELEMENT 1 OP
FLEXELEMENT 1 DPO
↓
FLEXELEMENT 8 PKP
FLEXELEMENT 8 OP
FLEXELEMENT 8 DPO
ELEMENT:
PHASE UV1 PKP
Phase UV
PHASE UV1 OP
PHASE UV1 DPO
PHASE UV1 PKP A
PHASE UV1 PKP B
PHASE UV1 PKP C
PHASE UV1 OP A
PHASE UV1 OP B
PHASE UV1 OP C
PHASE UV1 DPO A
PHASE UV1 DPO B
PHASE UV1 DPO C
PHASE UV2
ELEMENT:
SETTING GROUP ACT 1
↓
Setting Group
SETTING GROUP ACT 8
ELEMENT:
SYNC 1 DEAD S OP
Synchrocheck
SYNC 1 DEAD S DPO
SYNC 1 SYNC OP
SYNC 1 SYNC DPO
SYNC 1 CLS OP
SYNC 1 CLS DPO
SYNC 2
FIXED OPERANDS
Off
On
INPUTS/OUTPUTS:
Cont Ip 1
Contact Inputs
Cont Ip 2
↓
Cont Ip 1
Cont Ip 2
↓
INPUTS/OUTPUTS:
Cont Op 1
Contact Outputs,
Cont Op 2
↓
Current
(from detector on
Cont Op 1
Form-A output only)
Cont Op 2
↓
INPUTS/OUTPUTS:
Cont Op 1
Contact Outputs,
Cont Op 2
↓
Voltage
(from detector on
Cont Op 1
Form-A output only)
Cont Op 2
↓
INPUTS/OUTPUTS:
REMOTE INPUT 1 On
↓
Remote Inputs
REMOTE INPUT 32 On
INPUTS/OUTPUTS:
Virt Ip 1
↓
Virtual Inputs
Virt Ip 32
INPUTS/OUTPUTS:
Virt Op 1
↓
Virtual Outputs
Virt Op 64
REMOTE DEVICES
REMOTE DEVICE 1 On
↓
REMOTE DEVICE 16 On
REMOTE DEVICE 1 Off
↓
REMOTE DEVICE 16 Off
GE Multilin
OPERAND DESCRIPTION
FlexElement 1 has picked up
FlexElement 1 has operated
FlexElement 1 has dropped out
↓
FlexElement 8 has picked up
FlexElement 8 has operated
FlexElement 8 has dropped out
At least one phase of UV1 has picked up
At least one phase of UV1 has operated
At least one phase of UV1 has dropped out
Phase A of UV1 has picked up
Phase B of UV1 has picked up
Phase C of UV1 has picked up
Phase A of UV1 has operated
Phase B of UV1 has operated
Phase C of UV1 has operated
Phase A of UV1 has dropped out
Phase B of UV1 has dropped out
Phase C of UV1 has dropped out
Same set of operands as shown for PHASE UV1
Setting group 1 is active
↓
Setting group 8 is active
Synchrocheck 1 dead source has operated
Synchrocheck 1 dead source has dropped out
Synchrocheck 1 in synchronization has operated
Synchrocheck 1 in synchronization has dropped out
Synchrocheck 1 close has operated
Synchrocheck 1 close has dropped out
Same set of operands as shown for SYNC 1
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as 'Disable' by other features.
Logic = 1. Can be used as a test setting.
On
(will not appear unless ordered)
On
(will not appear unless ordered)
↓
Off
(will not appear unless ordered)
Off
(will not appear unless ordered)
↓
IOn
(will not appear unless ordered)
IOn
(will not appear unless ordered)
↓
IOff
(will not appear unless ordered)
IOff
(will not appear unless ordered)
↓
VOn
(will not appear unless ordered)
VOn
(will not appear unless ordered)
↓
VOff
(will not appear unless ordered)
VOff
(will not appear unless ordered)
↓
Flag is set, logic=1
↓
Flag is set, logic=1
On
Flag is set, logic=1
↓
On
Flag is set, logic=1
On
Flag is set, logic=1
↓
On
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
Flag is set, logic=1
↓
Flag is set, logic=1
C60 Breaker Management Relay
5.4 FLEXLOGIC™
5
5-35