GE C60 Instruction Manual page 125

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5 SETTINGS
c) AUXILIARY OV1 (AUXILIARY OVERVOLTAGE: ANSI 59X)
!"
PATH: SETTINGS
GROUPED ELEMENTS
# AUXILIARY OV1
#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This element is intended for monitoring overvoltage conditions of the auxiliary voltage. A typical application for this element
is monitoring the zero-sequence voltage (3V_0) supplied from an open-corner-delta VT connection. The nominal secondary
voltage of the auxiliary voltage channel entered under
is the p.u. base used when setting the pickup level.
AUXILIARY VT X5 SECONDARY
SETTING
AUX OV1
FUNCTION:
Disabled=0
Enabled=1
SETTING
AUX OV1 BLOCK:
Off=0
SETTING
AUX OV1 SIGNAL
SOURCE:
AUXILIARY VOLT (Vx)
GE Multilin
!
SETTING GROUP 1(8)
AUX OV1
FUNCTION: Disabled
AUX OV1 SIGNAL
SOURCE: SRC 1
AUX OV1 PICKUP:
0.300 pu
AUX OV1 PICKUP
DELAY: 1.00 s
AUX OV1 RESET
DELAY: 1.00 s
AUX OV1 BLOCK:
Off
AUX OV1
TARGET: Self-reset
AUX OV1
EVENTS: Disabled
SETTINGS
SETTING
AUX OV1 PICKUP:
RUN
AND
<
Vx Pickup
Figure 5–25: AUXILIARY OVERVOLTAGE SCHEME LOGIC
C60 Breaker Management Relay
5.5 GROUPED ELEMENTS
!"
!"
VOLTAGE ELEMENTS
AUXILIARY OV1
Range: Disabled, Enabled
Range: SRC 1, SRC 2,..., SRC 6
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
!"
!
SYSTEM SETUP
AC INPUTS
SETTING
AUX OV1 PICKUP
DELAY :
AUX OV1 RESET
DELAY :
t
PKP
t
RST
"!
"!
VOLTAGE BANK X5
FLEXLOGIC OPERANDS
AUX OV1 OP
AUX OV1 DPO
AUX OV1 PKP
827836A2.CDR
5-61
5