CHAPTER 5: SETTINGS
5.3.11.2 Calculation method 2: Block interval
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the programmed demand time interval, starting daily at 00:00:00 (that is, 12:00 am). The 1440 minutes per day is divided
into the number of blocks as set by the programmed time interval. Each new value of demand becomes available at the
end of each time interval.
5.3.11.3 Calculation method 2a: Block interval (with start demand interval logic trigger)
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the interval between successive Start Demand Interval logic input pulses. Each new value of demand becomes available at
the end of each pulse. Assign a FlexLogic operand to the
demand interval pulses.
If no trigger is assigned in the
calculation method 2. If a trigger is assigned, the maximum allowed time between two trigger signals is 60 minutes.
If no trigger signal appears within 60 minutes, demand calculations are performed and available, and the algorithm
resets and starts the new cycle of calculations. The minimum required time for trigger contact closure is 20 µs.
5.3.11.4 Calculation method 3: Rolling demand
This method calculates a linear average of the quantity (RMS current, real power, reactive power, or apparent power) over
the programmed demand time interval, in the same way as Block Interval. The value is updated every minute and
indicates the demand over the time interval just preceding the time of update.

5.3.12 User-programmable LEDs

5.3.12.1 Menu - Enhanced and standard front panels
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS
 USER-PROGRAMMABLE
 LEDS
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
Figure 5-50: Thermal demand characteristic
DEMAND TRIGGER
setting and the
DEMAND TRIGGER
 LED TEST
 TRIP & ALARM LEDS
 USER-PROGRAMMABLE
 LED 1
 USER-PROGRAMMABLE
 LED 48
setting to program the input for the new
is "Block Interval," use
CRNT DEMAND METHOD
See below
See page 5-122
See page 5-122
PRODUCT SETUP
5
5-119