There are 2 identical Breaker Failure menus available, numbered 1 and 2.
In general, a breaker failure scheme determines that a breaker signaled to trip has not cleared a fault within a definite time,
so further tripping action must be performed. Tripping from the breaker failure scheme should trip all breakers, both local
and remote, that can supply current to the faulted zone. Usually operation of a breaker failure element will cause clearing of
a larger section of the power system than the initial trip. Because breaker failure can result in tripping a large number of
breakers and this affects system safety and stability, a very high level of security is required.
GE Multilin
BF1 USE TIMER 3:
Yes
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
BF1 BKR POS1 φA/3P:
Off
BF1 BKR POS2 φA/3P:
Off
BF1 BREAKER TEST ON:
Off
BF1 PH AMP HISET
PICKUP: 1.050 pu
BF1 N AMP HISET
PICKUP: 1.050 pu
BF1 PH AMP LOSET
PICKUP: 1.050 pu
BF1 N AMP LOSET
PICKUP: 1.050 pu
BF1 LOSET TIME
DELAY:
0.000 s
BF1 TRIP DROPOUT
DELAY:
0.000 s
BF1 TARGET
Self-Reset
BF1 EVENTS
Disabled
BF1 PH A INITIATE:
Off
BF1 PH B INITIATE:
Off
BF1 PH C INITIATE:
Off
BF1 BKR POS1 φB
Off
BF1 BKR POS1 φC
Off
BF1 BKR POS2 φB
Off
BF1 BKR POS2 φC
Off
C60 Breaker Management Relay
5.5 GROUPED ELEMENTS
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
Range: FlexLogic™ operand
Valid only for 1-Pole breaker failure schemes.
Range: FlexLogic™ operand
Valid only for 1-Pole breaker failure schemes.
Range: FlexLogic™ operand
Valid only for 1-Pole breaker failure schemes.
Range: FlexLogic™ operand
Valid only for 1-Pole breaker failure schemes.
Range: FlexLogic™ operand
Valid only for 1-Pole breaker failure schemes.
Range: FlexLogic™ operand
Valid only for 1-Pole breaker failure schemes.
Range: FlexLogic™ operand
Valid only for 1-Pole breaker failure schemes.