2 PRODUCT DESCRIPTION
2.2
SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times below include the activation time of a trip rated Form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
NOTE
interfacing with other IEDs or power system devices via communications or different output contacts.
BREAKER FAILURE
Mode:
1-pole, 3-pole
Current Supv. Level:
Phase, Neutral
Current Supv. Pickup:
0.001 to 30.000 pu in steps of 0.001
Current Supv. DPO:
97 to 98% of Pickup
Current Supv. Accuracy:
0.1 to 2.0 × CT rating: ±0.75% of reading or ±1% of rated
(whichever is greater)
> 2 × CT rating:
±1.5% of reading
PHASE UNDERVOLTAGE
Pickup Level:
0.000 to 3.000 pu in steps of 0.001
Dropout Level:
102 to 103% of Pickup
Level Accuracy:
±0.5% of reading from 10 to 208 V
Curve Shapes:
GE IAV Inverse;
Definite Time (0.1s base curve)
Curve Multiplier:
Time Dial = 0.00 to 600.00 in steps of
0.01
Operate at < 0.90 × Pickup
Timing Accuracy:
±3.5% of operate time or ±4 ms (which-
ever is greater)
AUXILIARY UNDERVOLTAGE
Pickup Level:
0.000 to 3.000 pu in steps of 0.001
Dropout Level:
102 to 103% of Pickup
Level Accuracy:
±0.5% of reading from 10 to 208 V
Curve Shapes:
GE IAV Inverse
Definite Time
Curve Multiplier:
Time Dial = 0 to 600.00 in steps of 0.01
Timing Accuracy:
±3% of operate time or ±4 ms
(whichever is greater)
GE Multilin
AUXILIARY OVERVOLTAGE
Pickup Level:
Dropout Level:
Level Accuracy:
Pickup Delay:
Reset Delay:
Timing Accuracy:
Operate Time:
SYNCHROCHECK
Max Volt Difference:
Max Angle Difference:
Max Freq Difference:
Dead Source Function: None, LV1 & DV2, DV1 & LV2, DV1 or
AUTORECLOSURE
Two breakers applications
Single- and three-pole tripping schemes
Up to 2 reclose attempts before lockout
Selectable reclosing mode and breaker sequence
C60 Breaker Management Relay

2.2 SPECIFICATIONS

2.2.1 PROTECTION ELEMENTS

0.000 to 3.000 pu in steps of 0.001
97 to 98% of Pickup
±0.5% of reading from 10 to 208 V
0 to 600.00 s in steps of 0.01
0 to 600.00 s in steps of 0.01
±3% of operate time or ±4 ms
(whichever is greater)
< 30 ms at 1.10 × pickup at 60 Hz
0 to 100000 V in steps of 1
°
0 to 100
in steps of 1
0.00 to 2.00 Hz in steps of 0.01
DV2, DV1 xor DV2, DV1 & DV2 (L=Live,
D=Dead)
2
2-5