Autoreclose - GE C60 Instruction Manual

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5 SETTINGS
!"
PATH: SETTINGS
CONTROL ELEMENTS

# AUTORECLOSE

#
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
!"
!
AUTORECLOSE
AUTORECLOSE
AR FUNCTION:
Disabled
AR MODE:
1 & 3 Pole
AR MAX NUMBER OF
SHOTS: 2
AR BLOCK BKR1:
Off
AR CLOSE TIME BKR 1:
0.10 s
AR BKR MAN CLOSE:
Off
AR BLK TIME UPON MAN
CLS:
10.00 s
AR 1P INIT:
Off
AR 3P INIT:
Off
AR 3P TD INIT:
Off
AR MULTI-P FAULT:
Off
BKR ONE POLE OPEN:
Off
BKR 3 POLE OPEN:
Off
AR 3-P DEAD TIME 1:
0.50 s
AR 3-P DEAD TIME 2:
1.20 s
AR EXTEND DEAD T 1:
Off
AR DEAD TIME 1
EXTENSION: 0.50 s
AR RESET:
Off
AR RESET TIME:
60.00 s
AR BKR CLOSED:
Off
AR BLOCK:
Off
C60 Breaker Management Relay
5.6 CONTROL ELEMENTS
5.6.4 AUTORECLOSE
Range: Disabled, Enabled
Range: 1 & 3 Pole, 1 Pole, 3 Pole-A, 3 Pole-B
Range: 1, 2
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: 0 to 655.35 s in steps of 0.01
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5
5-67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents