5.6 CONTROL ELEMENTS
5 SETTINGS
For correct operation of the autoreclose scheme, the Breaker Control feature must be enabled and config-
ured properly. When the breaker reclose sequence is "1-2" or "2-1" the breaker that will reclose second in
sequence (breaker No. 2 for sequence 1-2 and breaker No. 1 for sequence 2-1) must be configured to trip
NOTE
three-pole for any type of fault
5
Figure 5–28: SINGLE-POLE AUTORECLOSE LOGIC (SHEET 1 OF 3)
5-74
C60 Breaker Management Relay
GE Multilin