GE C60 Instruction Manual page 237

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 9 of 29)
ADDR
REGISTER NAME
4051
Default Message Timeout
4052
Default Message Intensity
Communications (Read/Write Setting)
407E
COM1 minimum response time
407F
COM2 minimum response time
4080
Modbus Slave Address
4083
RS485 Com1 Baud Rate
4084
RS485 Com1 Parity
4085
RS485 Com2 Baud Rate
4086
RS485 Com2 Parity
4087
IP Address
4089
IP Subnet Mask
408B
Gateway IP Address
408D
Network Address NSAP
4097
Default GOOSE Update Time
4098
Ethernet Primary Fibre Channel Link Monitor
4099
Ethernet Secondary Fibre Channel Link Monitor
409A
DNP Port
409B
DNP Address
409C
DNP Client Addresses (2 items)
40A0
TCP Port Number for the Modbus protocol
40A1
TCP/UDP Port Number for the DNP Protocol
40A2
TCP Port Number for the UCA/MMS Protocol
40A3
TCP Port No. for the HTTP (Web Server) Protocol
40A4
Main UDP Port Number for the TFTP Protocol
40A5
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means "automatic") (2 items)
40A7
DNP Unsolicited Responses Function
40A8
DNP Unsolicited Responses Timeout
40A9
DNP Unsolicited Responses Max Retries
40AA
DNP Unsolicited Responses Destination Address
40AB
Ethernet Operation Mode
40AC
DNP User Map Function
40AD
DNP Number of Sources used in Analog points list
40AE
DNP Current Scale Factor
40AF
DNP Voltage Scale Factor
40B0
DNP Power Scale Factor
40B1
DNP Energy Scale Factor
40B2
DNP Other Scale Factor
40B3
DNP Current Default Deadband
40B4
DNP Voltage Default Deadband
40B5
DNP Power Default Deadband
40B6
DNP Energy Default Deadband
40B7
DNP Other Default Deadband
40B8
DNP IIN Time Sync Bit Period
40B9
DNP Message Fragment Size
40BA
DNP Client Address 3
40BC
DNP Client Address 4
40BE
DNP Client Address 5
40C0
DNP Communications Reserved (8 items)
40C8
UCA Logical Device Name
40D0
UCA Communications Reserved (16 items)
40E0
TCP Port Number for the IEC 60870-5-104 Protocol
40E1
IEC 60870-5-104 Protocol Function
GE Multilin
RANGE
10 to 900
0 to 3
0 to 1000
0 to 1000
1 to 254
0 to 11
0 to 2
0 to 11
0 to 2
0 to 4294967295
0 to 4294967295
0 to 4294967295
---
1 to 60
0 to 1
0 to 1
0 to 4
0 to 65519
0 to 4294967295
1 to 65535
1 to 65535
1 to 65535
1 to 65535
1 to 65535
0 to 65535
0 to 1
0 to 60
1 to 255
0 to 65519
0 to 1
0 to 1
1 to 6
0 to 5
0 to 5
0 to 5
0 to 5
0 to 5
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
1 to 10080
30 to 2048
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
---
0 to 1
1 to 65535
0 to 1
C60 Breaker Management Relay
B.3 MEMORY MAPPING
UNITS
STEP
FORMAT
s
1
F001
---
1
F101
ms
10
F001
ms
10
F001
---
1
F001
---
1
F112
---
1
F113
---
1
F112
---
1
F113
---
1
F003
---
1
F003
---
1
F003
---
---
F074
s
1
F001
---
1
F102
---
1
F102
---
1
F177
---
1
F001
---
1
F003
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F102
s
1
F001
---
1
F001
---
1
F001
---
1
F192
---
1
F102
---
1
F001
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F194
---
1
F001
---
1
F001
---
1
F001
---
1
F001
---
1
F001
min
1
F001
---
1
F001
---
1
F003
---
1
F003
---
1
F003
---
1
F001
---
---
F203
---
1
F001
---
1
F001
---
1
F102
DEFAULT
300
0 (25%)
0
0
B
254
5 (19200)
0 (None)
5 (19200)
0 (None)
56554706
4294966272
56554497
0
60
0 (Disabled)
0 (Disabled)
0 (NONE)
255
0
502
20000
102
80
69
0
0 (Disabled)
5
10
1
0 (Half-Duplex)
0 (Disabled)
1
2 (1)
2 (1)
2 (1)
2 (1)
2 (1)
30000
30000
30000
30000
30000
1440
240
0
0
0
0
"UCADevice"
0
2404
0 (Disabled)
B-17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents