GE C60 Instruction Manual page 241

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 13 of 29)
ADDR
REGISTER NAME
478A
Synchrocheck Live V1 Min Volt
478B
Synchrocheck Live V2 Min Volt
478C
Synchrocheck Target
478D
Synchrocheck Events
478E
Synchrocheck Block
478F
Synchrocheck X Reserved
4790
...Repeated for module number 2
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (8 modules)
4C00
User display top line text
4C0A
User display bottom line text
4C14
Modbus addresses of displayed items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for module number 2
4C40
...Repeated for module number 3
4C60
...Repeated for module number 4
4C80
...Repeated for module number 5
4CA0
...Repeated for module number 6
4CC0
...Repeated for module number 7
4CE0
...Repeated for module number 8
FlexLogic™ (Read/Write Setting)
5000
FlexLogic Entry (512 items)
FlexLogic™ Timers (Read/Write Setting) (32 modules)
5800
Timer x Type
5801
Timer x Pickup Delay
5802
Timer x Dropout Delay
5803
Timer x Reserved (5 items)
5808
...Repeated for module number 2
5810
...Repeated for module number 3
5818
...Repeated for module number 4
5820
...Repeated for module number 5
5828
...Repeated for module number 6
5830
...Repeated for module number 7
5838
...Repeated for module number 8
5840
...Repeated for module number 9
5848
...Repeated for module number 10
5850
...Repeated for module number 11
5858
...Repeated for module number 12
5860
...Repeated for module number 13
5868
...Repeated for module number 14
5870
...Repeated for module number 15
5878
...Repeated for module number 16
5880
...Repeated for module number 17
5888
...Repeated for module number 18
5890
...Repeated for module number 19
5898
...Repeated for module number 20
58A0
...Repeated for module number 21
58A8
...Repeated for module number 22
58B0
...Repeated for module number 23
58B8
...Repeated for module number 24
58C0
...Repeated for module number 25
58C8
...Repeated for module number 26
58D0
...Repeated for module number 27
GE Multilin
RANGE
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 65535
0 to 65535
0 to 65535
---
---
0 to 65535
---
0 to 65535
0 to 2
0 to 60000
0 to 60000
0 to 65535
C60 Breaker Management Relay
B.3 MEMORY MAPPING
UNITS
STEP
FORMAT
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
---
1
F001
---
1
F001
---
---
F202
---
---
F202
---
1
F001
---
---
F001
---
1
F300
---
1
F129
---
1
F001
---
1
F001
---
1
F001
DEFAULT
70
70
0 (Self-reset)
0 (Disabled)
0
B
0
0
" "
" "
0
0
16384
0 (millisecond)
0
0
0
B-21