GE C60 Instruction Manual page 98

Multilin breaker management relay ur series
Hide thumbs Also See for C60:
Table of Contents

Advertisement

5.4 FLEXLOGIC™
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–10: C60 FLEXLOGIC™ OPERANDS (Sheet 1 of 3)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
AR ENABLED
Autoreclose
AR DISABLED
(1P/3P)
AR RIP
AR 1-P RIP
AR 3-P/1 RIP
AR 3-P/2 RIP
AR LO
AR BKR1 BLK
AR BKR2 BLK
AR CLOSE BKR1
AR CLOSE BKR2
AR FORCE 3-P TRIP
AR SHOT CNT > 0
AR ZONE 1 EXTENT
AR INCOMPLETE SEQ
AR RESET
ELEMENT:
AUX OV1 PKP
Auxiliary OV
AUX OV1 DPO
AUX OV1 OP
ELEMENT:
AUX UV1 PKP
Auxiliary UV
AUX UV1 DPO
AUX UV1 OP
ELEMENT:
BKR ARC 1 OP
Breaker Arcing
BKR ARC 2 OP
ELEMENT
BKR FAIL 1 RETRIPA
(Breaker Failure)
BKR FAIL 1 RETRIPB
BKR FAIL 1 RETRIPC
5
BKR FAIL 1 RETRIP
BKR FAIL 1 T1 OP
BKR FAIL 1 T2 OP
BKR FAIL 1 T3 OP
BKR FAIL 1 TRIP OP
BKR FAIL 2...
ELEMENT:
BREAKER 1 OFF CMD
Breaker Control
BREAKER 1 ON CMD
BREAKER 1 φA CLSD
BREAKER 1 φB CLSD
BREAKER 1 φC CLSD
BREAKER 1 CLOSED
BREAKER 1 OPEN
BREAKER 1 DISCREP
BREAKER 1 TROUBLE
BREAKER 1 MNL CLS
BREAKER 1 TRIP A
BREAKER 1 TRIP B
BREAKER 1 TRIP C
BREAKER 1 ANY P OPEN
BREAKER 1 ONE P OPEN
BREAKER 1 OOS
BREAKER 2
ELEMENT:
Counter 1 HI
Digital Counter
Counter 1 EQL
Counter 1 LO
Counter 8 HI
Counter 8 EQL
Counter 8 LO
ELEMENT:
Dig Element 1 PKP
Digital Element
Dig Element 1 OP
Dig Element 1 DPO
Dig Element 16 PKP
Dig Element 16 OP
Dig Element 16 DPO
ELEMENT:
SRCx 50DD OP
Disturbance
Detector
5-34
OPERAND DESCRIPTION
Autoreclosure is enabled and ready to perform
Autoreclosure is disabled
Autoreclosure is in "Reclose in Progress" state
A single-pole reclosure is in progress
A three-pole reclosure is in progress, via DEAD TIME 1
A three-pole reclosure is in progress, via DEAD TIME 2
Autoreclosure is in lockout state
Reclosure of Breaker 1 is blocked
Reclosure of Breaker 2 is blocked
Reclose Breaker 1 signal
Reclose Breaker 2 signal
Force any trip to a three-phase trip
The first "CLOSE BKR X" signal has been issued
The Zone 1 Distance function must be set to the extended overreach value
The incomplete sequence timer timed out
AR has been reset either manually or by the reset timer
Auxiliary Overvoltage element has picked up
Auxiliary Overvoltage element has dropped out
Auxiliary Overvoltage element has operated
Auxiliary Undervoltage element has picked up
Auxiliary Undervoltage element has dropped out
Auxiliary Undervoltage element has operated
Breaker Arcing 1 is operated
Breaker Arcing 2 is operated
Breaker Failure 1 re-trip phase A (only for 1-pole schemes)
Breaker Failure 1 re-trip phase B (only for 1-pole schemes)
Breaker Failure 1 re-trip phase C (only for 1-pole schemes)
Breaker Failure 1 re-trip 3-phase
Breaker Failure 1 Timer 1 is operated
Breaker Failure 1 Timer 2 is operated
Breaker Failure 1 Timer 3 is operated
Breaker Failure 1 trip is operated
Same set of operands as shown for BKR FAIL 1
Breaker 1 OFF command
Breaker 1 ON command
Breaker 1 phase A is closed
Breaker 1 phase B is closed
Breaker 1 phase C is closed
Breaker 1 is closed
Breaker 1 is open
Breaker 1 has discrepancy
Breaker 1 trouble alarm
Breaker 1 manual close
Breaker 1 trip phase A command
Breaker 1 trip phase B command
Breaker 1 trip phase C command
At least one pole of Breaker 1 is open
Only one pole of Breaker 1 is open
Breaker 1 is out of service
Same set of operands as shown for BREAKER 1
Digital Counter 1 output is 'more than' comparison value
Digital Counter 1 output is 'equal to' comparison value
Digital Counter 1 output is 'less than' comparison value
Digital Counter 8 output is 'more than' comparison value
Digital Counter 8 output is 'equal to' comparison value
Digital Counter 8 output is 'less than' comparison value
Digital Element 1 is picked up
Digital Element 1 is operated
Digital Element 1 is dropped out
Digital Element 16 is picked up
Digital Element 16 is operated
Digital Element 16 is dropped out
Source x Disturbance Detector is operated
C60 Breaker Management Relay
5 SETTINGS
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents