Smoke Detector Test; Check Or Trouble Messages - Honeywell VISTA-128BPT Installation And Setup Manual

Commercial burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-128BPT:
Table of Contents

Advertisement

VISTA-128BPT/128BPT-SIA/250BPT INSTALLATION AND SETUP GUIDE

Smoke Detector Test

All smoke detectors must be tested monthly by pressing the TEST button located on the detector. If the
TEST button does not cause the detector to activate it must be replaced immediately.
Trouble Conditions

Check or Trouble Messages

Display
CHECK or TRBL
(as per field 1∗07)
CHECK 8XX
XX = 00-30
CHECK 9XX
XX = 00-99
If the problem has been corrected, enter an OFF sequence (Security Code + OFF) twice to clear the
display.
Power Failure
Display
AC LOSS
POWER LED is off
Other System Messages
Display
COMM FAILURE
LO BAT
SYSTEM LO BAT
RCVR SETUP
ERROR
MODEM COMM
Description
This indicates that a problem exists on the zone number displayed. Zone trouble may be
caused by one of the following conditions:
A hardwired fire zone is open (broken wire).
A zone programmed for tamper on Open/Short has been tampered.
A Day/Night zone (zone type 5) is faulted.
A polling loop zone is not seen by the control panel.
A polling loop zone has been tampered (cover removed on a V-PLEX device).
A wireless zone has not checked in during the time programmed in field 1∗31.
A 5800 Series transmitter has been tampered (cover removed).
This indicates a trouble on a peripheral device (connected to the panel's keypad
terminals) of the corresponding device address (00-30).
This indicates that a system trouble exists (RF receiver, bell output, etc.).
Description
This indicates that the system is operating on battery power only. Check to see that
the circuit breaker for the branch circuit that your system's transformer is wired to has
not been accidentally turned off.
Instruct the user to call a service representative immediately if AC power cannot be
restored.
Description
This indicates that a failure occurred in the telephone communication portion of your
system.
This indicates that a low-battery condition exists in the wireless transmitter displayed.
Pressing any key silences the audible warning sound.
This indicates that a low-battery condition exists with the system's backup battery.
This indicates that the system has more wireless zones programmed than the wireless
receiver can support.
If this is not corrected, none of the zones in the system will be protected. If additional
wireless zones are desired, use an appropriate receiver.
This indicates that the control is on-line with a remote computer.