Installing ECP Devices

Supports up to 31 addressable devices (00-30), keypads, RF receivers, relay modules, etc. All devices programmable
to be Supervised (Zone 8XX), refer to the Program Guide for programming procedure.
NOTE: You may need to use an auxiliary power supply if the 750mA aux. output is exceeded. See the
"Supplementary Power Supply for Additional ECP Devices" section.
Alpha Keypad
Wire Gauge
Length
#22 gauge
450 feet
#20 gauge
700 feet
#18 gauge
1100 feet
#16 gauge
1750 feet
Alpha Keypad
Wire Gauge
Length
#22 gauge
225 feet
#20 gauge
350 feet
#18 gauge
750 feet
#16 gauge
875 feet
Devices maybe daisy chained. However, if the limits above are exceeded,
sluggishness or lack of response may be experienced.
NOTE:
DI meters a minimal voltage
spike on return data to the
panel (i.e. button press),
otherwise during idle state it
reads 0VDC.
Wiring and Troubleshooting
If an ECP device is not working, verify the following:
Programming has been properly configured (devices enabled in *93 Device Programming).
Addressing of the ECP device has been configured properly.
a.
Device dipswitches addressing
b.
Software programmable addressing (i.e. keypad addressing by pressing 1 and 3 at the same time)
Wiring is correct (i.e. DO and DI are not reversed).
ECP v
oltages are correct (see Figure 5 above for voltage requirements).
NOTE: Constant voltage (≥ 1vdc) on DI (green) causes no response from device.
Devices using an external power source require a common ground to the control panel.
ECP Wire Run Length/Gauge Table (Unshielded)
Touch Screen (AUI)
Wire Gauge
Length
#22 gauge
150 feet
#20 gauge
240 feet
#18 gauge
350 feet
#16 gauge
550 feet
ECP Wire Run Length/Gauge Table (Conduit/Shielded)
Touch Screen (AUI)
Wire Gauge
Length
#22 gauge
75 feet
#20 gauge
120 feet
#18 gauge
175 feet
#16 gauge
225 feet

Figure 5: ECP Connections and Voltage Requirements

SECTION 4: INSTALLING THE CONTROL
4204/4204CF Relay Boards
Wire Gauge
Length
#22 gauge
125 feet
#20 gauge
200 feet
#18 gauge
300 feet
#16 gauge
500 feet
4204/4204CF Relay Boards
Wire Gauge
Length
#22 gauge
62 feet
#20 gauge
100 feet
#18 gauge
150 feet
#16 gauge
250 feet
Devices must be homerun to the control panel
4-3
5881/5883 RF Receivers
Wire Gauge
Length
#22 gauge
220 feet
#20 gauge
N/A
#18 gauge
550 feet
#16 gauge
N/A
5881/5883 RF Receivers
Wire Gauge
Length
#22 gauge
110 feet
#20 gauge
N/A
#18 gauge
225 feet
#16 gauge
N/A