Figure 35: 1361/1361-GT (Canada 1361CN/1361CN-GT) Transformer and Battery Connections
Panel Earth Ground Connections
In order for the lightning transient protective devices in this product to be effective, the designated earth ground
terminal (terminal 30) must be terminated to a good earth ground. Recommended wire gauge for the ground
connection is #16 AWG; run no farther than 30 feet. The following are examples of good earth grounds available at
most installations:
• Metal Cold Water Pipe: Use a noncorrosive metal strap (copper is recommended) firmly secured to the pipe to
which the ground lead is electrically connected and secured.
• AC Power Outlet Ground: Available from 3-prong, 120VAC power outlets only. To test the integrity of the ground
terminal, use a three-wire circuit tester with neon lamp indicators, such as the UL-Listed Ideal Model 61-035, or
equivalent, available at most electrical supply stores.
The panel requires the earth ground connection for its lightning transient protection devices.
SECTION 4: INSTALLING THE CONTROL
4-37