Outputs 2 and 4
Place the + (positive) meter lead on the auxiliary positive terminal/wire of the power supply and the – (negative) the
trigger.
•
In the non-triggered state the voltage is 0VDC
•
When the trigger is activated the control will apply the ground reference to the trigger and your meter reads
12VDC.
•
See the Remote Keyswitch section below (figure 26).
Figure 24: Smoke Reset Using Low Sensitivity Relay
4-23
SECTION 4: INSTALLING THE CONTROL