VISTA-128BPT/128BPT-SIA/250BPT INSTALLATION AND SETUP GUIDE
NOTE: If using Total Connect Remote Interactive
Services, the virtual keypad must be assigned
to a burglary partition, and the GOTO feature
(program field 2∗18) must be "0" (disabled) for
partition 1 (the fire partition) so that the Fire
system cannot be accessed remotely. This is
the system default setting.
Anti-Mask is used if an interior zone types 04
(interior) or 10 (interior with delay) and input type
Peripheral Devices
• Supports up to 31 addressable devices, (keypads,
RF receivers, relay modules, etc.).
• Supervises devices (keypads, RF receivers, and
relay modules) and individual relays (up to 32), as
well as system zones (RF receivers and keypad
panics).
Arming/Disarming and Bypassing
• Can arm the system with zones faulted (Vent
Zone). These zones are automatically bypassed
and can be programmed to automatically
unbypass when the zone restores.
• Can arm with entry/exit and interior type zones
faulted (Arm w/Fault). These zones must be
restored before the exit delay expires, otherwise an
alarm is generated.
• Vent zones cannot be used in UL
installations.
• You must disable the Force Arm
UL
option (used in conjunction with the
Arm w/Fault option), in UL
installations.
You must disable the Force Arm option
ULC
(used in conjunction with the Arm
w/Fault option), in ULC Installations.
• Provides global arming capability (ability to arm all
partitions the user code has access to in one
command).
• Can Quick Exit an armed premises without having
to disarm and then rearm the system.
06 (serial poll) are selected. The trouble report
code is used to report the masking.
A Smart contact option that may be selected for
devices that support this feature such as the
5193SDT Smoke Detector or PIRs.
Battery sensing hardware that can sense when the
battery voltage is too low and prevents deep
discharging from not occurring.
• Provides 96 outputs using 4204 Relay Modules
and V-PLEX Relay Modules that can activate
outputs in response to system events (alarm
condition), at a specific time of day, at random
times, and manually using the #70 Relay
Command Mode.
• Supports a Momentary Keyswitch on any one of
the system's eight partitions, using zone seven
(Event/Actions).
Quick Exit is not permitted for use with
UL
the VISTA-128BPT/VISTA-250BPT
Control Panel in a UL installation.
• Can be armed in one of three STAY modes or
Instant modes, automatically bypassing specific
burglary zones regardless of the zone response
type.
• Can automatically bypass specific zones if no one
exits the premises after arming (Auto-STAY). Auto-
STAY will not occur if the system is armed via an RF
transmitter, scheduling, access control, keyswitch,
RS232 (TB4) automation or downloading.
• Can bypass a group of zones with one set of
keystrokes.
• Supports Exit Error Logic, whereby the system can
tell the difference between a regular alarm and an
alarm caused by leaving an entry/exit door open. If
the system is not subsequently disarmed, faulted
E/E zone(s) and/or interior zones are bypassed
and the system arms.
• Supports Recent Close report, which is designed
to notify the central station that an alarm has
occurred within 2 minutes after the exit delay has
expired.
2-2