Zone Technical Specifications
Zone(s)
Specifications
1
Zone one is rated for 10-14VDC at 25mA. Voltages:
Resistor intact:
Resistor removed:
Voltage drop:
Detectors.
2-7
EOLR CONFIG:
Maximum Loop Current (Loop Short):
Maximum Loop Voltage (Loop Open):
Loop Short:
Loop Normal:
Loop Open:
Response Time:
Zone resistance (Excluding EOLR):
8
EOLR CONFIG:
Maximum Loop Current:
Maximum Loop V:
Loop Short:
Loop Normal:
Loop Open:
Response Time:
Zone resistance (Excluding EOLR):
Zone 8 can support 2-wire non-V-PLEX glassbreak detectors. The zone provides enough standby current
to power up to 50 two-wire glassbreak detectors meeting the requirements listed below.
Standby Voltage:
Standby Resistance:
detectors in parallel)
Alarm Resistance:
Alarm Current:
Reset Time:
NOTES:
You can use detectors that exceed 1.1k ohms in alarm, provided they maintain a voltage drop of
less than 3.8 volts in alarm.
The ADEMCO ASC-SS1 detector has been tested and found to be compatible with these ratings.
SECTION 4: INSTALLING THE CONTROL
12.9VDC
13.5VDC
0 for 8 seconds on this terminal to reset 2-wire Smoke
7.4mA
13.3VDC
0V - 1.5V - 300 ohms total resistance)
4.2 - 6.8V, 1.2k - 2.6k
7.2V - 13.3V, 3k – Infinity
350-500mSec
300 OHMS MAXIMUM
9mA
13.3VDC
0 - 2.2V - (0 - 300 ohms)
5 - 9V (0.9k - 3.4k)
10V - 13.3V, 3.8k – Infinity
350-500mSec
100 OHMS MAXIMUM
5VDC -13.8VDC
Greater than 20k ohms (equivalent resistance of all
Less than 1.1k ohms (see note below)
2mA - 10mA
Less than 6 seconds
4-19