3.1 ENERVISTA 650 SETUP SOFTWARE INTERFACE 3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
Table 3.20: ACTUAL VALUES INCLUDED IN THE PROTECTION MENU
PROTECTION
3
Table 3.21: DIFFERENT CONTROL ACTUAL VALUES INCLUDED IN THE CONTROL ELEMENTS MENU FOR
FIRMWARE VERSION BELOW 7.50
CONTROL
ELEMENTS
3-32
Information related to the status of the frames sent through PRP and
Redundancy
HSR. Also information related to the status of RSTP port.
Protection Blocks
This screen shows all the protection element blocks available. Protection
elements block signals can be configured at "Setpoint>Relay
Configuration > Protection Elements".
Phase Current
Protection status signals (pickups and operations) for time overcurrent,
instantaneous overcurrent and directional protection functions for phase
current.
Neutral Current
Protection status signals (pickups and operations) for time overcurrent,
instantaneous overcurrent and directional protection functions for neutral
current (calculated from phases).
Ground Current
Protection status signals (pickups and operations) for time overcurrent,
instantaneous overcurrent and directional protection functions for ground
current (measured from 4
Sensitive Ground
Protection status signals (pickups and operations) for time overcurrent,
Current
instantaneous overcurrent, isolated and directional protection functions
for ground current (measured from 5
Negative Sequence
Protection status signals (pickups and operations) for negative sequence
Current
time overcurrent function.
Thermal Model
Protection status signals for thermal model. Reset, alarm and operation
signals for phases and for unit, besides the thermal image values in
percentage for all phases and units.
Voltage
Protection status signals (pickups and operations) for all voltage
functions, undervoltage, overvoltage, neutral overvoltage, negative
sequence overvoltage and auxiliary under and over voltage.
Power
Protection status signals (pickups and operations) for forward, directional
and wattmetric ground fault (high and low) power units, and power factor
status. Power values for 32N High and Low functions (in watts).
Frequency
Status signals (pickups and operations) for under, overfrequency and
frequency rate of change units.
Synchrocheck
Status signals for synchrocheck function (25).
Autoreclose
Status signals for autoreclose function (79). Close signal, recloser status
(ready, lockout, etc.), block signals after each shot.
Breaker Failure
Status signals for breaker failure function (50BF).
VT Fuse Failure
Fuse failure detection signal.
Broken Conductor
Status signals (pickups and operations) for broken conductor (I2/I1).
Setting Groups
Status signals (activations and blocks) for the relay setting group change.
By default the "setting group" setting is disabled and all the grouped
elements can be enabled at the same time.
Locked Rotor
Status signals (pickups and operations) for locked rotor units.
Pulse Counters
Status signals for pulse counters units.
Analog Comparator
Status signals for analog comparator units.
Load Encroachment
Status signals (pickups and operations) for load encroachment units.
Max.Number of Starts
Status signal for number of starts operations
Digital Counters
Status signals for the Digital Counter units.
Cold Load Pickup
Status signals for the Cold Load Pickup Function.
F650 Digital Bay Controller
th
current input).
th
current input).
GEK-106310AE