5 BOOTCODE AND FIRMWARE UPGRADE
5.1 UPGRADE FROM VERSION BELOW V7.00.
10. TO COMPLETE THE PROCEDURE, SWITCH OFF AND BACK ON THE RELAY WHEN REQUIRED BY THE
PROGRAM.
11. SET CALIBRATION SETTINGS (FROM THE PC TO THE RELAY) (for versions lower than 1.50).
12. THE SETTINGS AND CONFIGURATION ARE NOW SET TO FACTORY DEFAULT.
13. SEND THE NEW SETTINGS AND CONFIGURATION FILES TO THE RELAY IF NECESSARY.
(*) The boot code upgrade must be performed using a crossed copper cable (RJ45) connected to the PC. It is not
necessary to modify the internal fiber/cable switch, as the upgrade is carried out at 10 Mb/s, and thus there is not cable/
fiber conflict.This fact does not apply to the firmware upgrade, which can be performed either with the Ethernet fiber
connection, or with the cable connection.
Note: Please see chapter 13 F650 TROUBLESHOOTING GUIDE if there is any problem during the upgrading
process.
5
GEK-113000AE
F650 Digital Bay Controller
5-21